Notifier FMM-1 Intelligent Addressable Monitor Module User Manual

Model: FMM-1

1. تعارف اور اوورview

The Notifier FMM-1 is an intelligent addressable monitor module designed for use with Notifier's ONYX series and other compatible fire alarm control panels. This module allows conventional alarm initiating devices, such as manual pull stations, normally open contact devices, or waterflow switches, to be connected to an intelligent fire alarm system. It monitors the status of these devices and reports their condition (normal, alarm, or trouble) back to the control panel.

The FMM-1 module is a crucial component for integrating existing conventional devices into modern addressable fire detection systems, providing precise location identification for alarms and troubles.

سامنے والا view of the Notifier FMM-1 Intelligent Addressable Monitor Module, showing the Notifier by Honeywell logo and two small indicator lights.

شکل 1: سامنے view of the Notifier FMM-1 module. This image displays the module's front face, featuring the "Notifier by Honeywell" branding and two small circular indicators, likely for status or activity.

2. سیٹ اپ اور انسٹالیشن

Installation of the FMM-1 module should only be performed by qualified personnel in accordance with all local and national electrical codes, and the manufacturer's instructions. Ensure that all power to the fire alarm control panel and associated circuits is disconnected before beginning installation.

2.1 چڑھنا

The FMM-1 module is designed for mounting in a standard 4-inch square, 2-1/8 inch deep electrical box. It can also be mounted in a surface-mount box (SMB500) or a standard 1-gang box. The module includes mounting tabs for secure installation.

آگے اور پیچھے view of the Notifier FMM-1 module, showing the white plastic cover and the grey metal base with wiring terminals.

Figure 2: Front and back components of the Notifier FMM-1 module. This image illustrates both the front cover and the rear mounting plate, which houses the terminal connections for wiring.

2.2 وائرنگ

The FMM-1 module connects to the Signaling Line Circuit (SLC) of the fire alarm control panel and to the conventional initiating device circuit (IDC). Refer to the specific wiring diagrams provided with the module and the fire alarm control panel for correct connections. Ensure proper polarity for all connections.

Close-up of the back of the Notifier FMM-1 module, showing wiring terminals, model number, and regulatory markings like UL Listed and FM Approved.

شکل 3: پیچھے view of the Notifier FMM-1 module with wiring details. This image provides a clear view of the terminal block for connecting to the fire alarm system's Signaling Line Circuit (SLC) and the initiating device circuit (IDC), along with product labels and certifications.

After wiring, verify all connections are secure and correct before applying power to the system.

3. آپریٹنگ اصول

Once properly installed and addressed, the FMM-1 module operates by continuously monitoring the connected conventional initiating device circuit. It communicates the status of this circuit to the intelligent fire alarm control panel via the SLC.

The module's LED indicators (if present) may provide local visual indication of its status, such as flashing during normal operation or solid during an alarm/trouble condition. Refer to the specific product documentation for LED behavior.

4 دیکھ بھال

The Notifier FMM-1 module is designed for reliable, long-term operation with minimal maintenance. However, regular system-wide inspections and testing are crucial for ensuring the continued proper functioning of the fire alarm system.

Any maintenance or repair work beyond simple visual inspection and cleaning should be performed by a certified fire alarm technician.

5 خرابیوں کا سراغ لگانا

If the FMM-1 module or its connected devices are not functioning as expected, consider the following troubleshooting steps. Always ensure power is disconnected before inspecting wiring.

علامتممکنہ وجہحل
Module reports trouble condition.Open circuit, short circuit, or ground fault on IDC; incorrect EOLR; module addressing error.Verify IDC wiring for breaks or shorts. Check EOLR value and placement. Confirm module address is unique and correctly set.
Module not communicating with control panel.Incorrect SLC wiring; module address conflict; faulty module.Check SLC wiring for proper polarity and continuity. Ensure no duplicate addresses on the SLC. If issues persist, module may need replacement.
Connected device does not report alarm.Faulty initiating device; incorrect IDC wiring; module not configured correctly.Test the initiating device directly. Verify IDC wiring to the device. Confirm module programming in the control panel.

For complex issues or if troubleshooting steps do not resolve the problem, contact a certified fire alarm technician or Notifier technical support.

6. وضاحتیں

The following are key specifications for the Notifier FMM-1 Intelligent Addressable Monitor Module:

Notifier FMM-1 module in its original packaging, alongside a small instruction manual and a few small components.

Figure 4: Notifier FMM-1 module as packaged. This image shows the module, its clear plastic packaging, and the included installation and maintenance instructions, along with minor accessories.

7. وارنٹی اور سپورٹ

For specific warranty information regarding the Notifier FMM-1 Intelligent Addressable Monitor Module, please refer to the warranty documentation provided with your purchase or contact your authorized Notifier distributor or reseller. Warranty terms typically cover defects in materials and workmanship for a specified period from the date of purchase.

For technical support, installation assistance, or service inquiries, please contact Notifier's official customer support channels or your certified fire alarm system installer. Always provide your product model number (FMM-1) and any relevant system details when seeking support.

Notifier Official Webسائٹ: www.notifier.com

متعلقہ دستاویزات - FMM-1

پریview NOTIFIER NFS-3030 Intelligent Addressable Fire Alarm System | Technical Data Sheet
Explore the NOTIFIER NFS-3030, an intelligent addressable fire alarm control panel from the ONYX Series. Engineered for medium to large facilities, it offers advanced detection, modularity, and extensive device support for critical fire safety applications.
پریview نوٹیفائر NFS-320 ذہین ایڈریس ایبل فائر الارم سسٹم ڈیٹا شیٹ
نوٹیفائر NFS-320 انٹیلیجنٹ ایڈریس ایبل فائر الارم سسٹم کے لیے جامع ڈیٹا شیٹ، اس کی خصوصیات، ذہین سینسنگ کی صلاحیتوں، فلیش اسکین پروٹوکول، سسٹم کی وضاحتیں، مطابقت پذیر آلات، اور ایجنسی کی منظوریوں کی تفصیل۔
پریview نوٹیفائر NFS-640 ذہین ایڈریس ایبل فائر الارم سسٹم ڈیٹا شیٹ
تفصیل سے اوپرview of the Notifier NFS-640 Intelligent Addressable Fire Alarm Control Panel, covering its features, advanced FlashScan® protocol, intelligent sensing capabilities, programming options, system modules, and comprehensive technical specifications.
پریview نوٹیفائر AM-8000 انٹیلجنٹ ایڈریس ایبل فائر ڈیٹیکشن انسٹالیشن دستی
یہ انسٹالیشن مینوئل نوٹیفائر AM-8000 انٹیلجنٹ ایڈریس ایبل فائر ڈیٹیکشن سسٹم کے لیے جامع رہنمائی فراہم کرتا ہے۔ یہ نظام پر محیط ہے۔view، تکنیکی وضاحتیں، برقی خصوصیات، تنصیب کے طریقہ کار، وائرنگ کے خاکے، بجلی کی فراہمی کا حساب، جانچ، اور دیکھ بھال۔
پریview FlashScan® ڈیٹا شیٹ کے ساتھ نوٹیفائر AFC-600 ذہین ایڈریس ایبل فائر الارم کنٹرول پینل
نوٹیفائر AFC-600 انٹیلیجنٹ ایڈریس ایبل فائر الارم کنٹرول پینل کے لیے جامع ڈیٹا شیٹ، جس میں اس کی خصوصیات، تصریحات، سسٹم کی صلاحیت، پروگرامنگ کے اختیارات، ہم آہنگ آلات، اور ایجنسی کی منظوریوں کی تفصیل ہے۔ FlashScan® پروٹوکول اور AWACS™™ سینسنگ ٹیکنالوجی کے بارے میں معلومات پر مشتمل ہے۔
پریview NOTIFIER AFP-200 اینالاگ فائر پینل - تکنیکی وضاحتیں اور خصوصیات
تفصیل سے اوپرview NOTIFIER AFP-200 اینالاگ فائر پینل کا، اس کی خصوصیات، سسٹم کی صلاحیت، وضاحتیں، ہم آہنگ آلات، اور پروگرامنگ کے طریقوں کا احاطہ کرتا ہے۔ ایجنسی کی فہرست اور مصنوعات کی معلومات پر مشتمل ہے۔