Systemair K 125M Sileo

Systemair K 125M Sileo Duct Fan

ہدایت نامہ

1. تعارف

This manual provides detailed instructions for the installation, operation, and maintenance of the Systemair K 125M Sileo duct fan. The K-series fans are designed for efficient air handling in duct systems, featuring robust construction and reliable performance. Please read this manual thoroughly before installation and operation to ensure safe and correct use of the product.

2. حفاظتی معلومات

Always adhere to local electrical codes and safety regulations during installation and operation. Disconnect power before performing any maintenance or installation procedures.

  • The fan is equipped with built-in thermal contacts with automatic reset to protect the motor from overheating.
  • The airtight, folded galvanized steel housing (leak rate according to tightness class C, EN 12237:2003) allows for installation in damp rooms and outdoor areas.
  • The motor has a protection class of IP44.
  • مناسب گراؤنڈنگ کو یقینی بنائیں۔
  • اگر کوئی حصہ خراب ہو جائے تو پنکھا نہ چلائیں۔

3. مصنوعات کی خصوصیات

The Systemair K 125M Sileo duct fan offers the following key features:

  • Speed-Controllable: Can be controlled using a stepless thyristor or a 5-step transformer.
  • Integrated Thermal Protection: Built-in thermal contacts with automatic reset for motor safety.
  • لچکدار تنصیب: Installation is possible in any mounting position.
  • Outdoor and Damp Room Use: بیرونی اور ڈی کے لیے موزوں ہے۔amp environments due to its airtight housing and IP44 motor protection.
  • قابل اعتماد اور دیکھ بھال سے پاک: Designed for dependable operation with minimal maintenance requirements.
  • موثر ڈیزائن: Features backward-curved impeller blades and external rotor motors for optimal performance.
  • آسان نصب: Includes a mounting bracket for straightforward installation and removal.

4. تکنیکی تفصیلات

پیرامیٹرقدر
ماڈلK 125M Sileo
والیومtage230V
تعدد50Hz
مرحلہ1~
Electrical Power Consumption (P1)28.2W
کرنٹ0.164A
Max. Volume Flow187m³/h
رفتار2491 1/منٹ
وزن2.3 کلو
Max. Medium Temperature70°C
Max. Medium Temperature (Speed Controlled)70°C
Sound Pressure Level at 3m (20m³ Sabin)34.2dB(A)
موصلیت کی کلاسB
Protection Class, Motorآئی پی 44
کنکشن قطر۔125 ملی میٹر
Energy Class (Basic Unit)F
Energy Class (Basic Unit Option)C
ErP Readyای آر پی 2018
کارخانہ دارسسٹم ایئر
ASINB07ZP91RP2
صنعت کار حوالہ103573
Table showing maximum efficiency and operating data for the Systemair K 125M Sileo fan

Figure 4.1: Maximum Efficiency and Operating Data Table. This table provides detailed performance metrics including airflow, static pressure, power consumption, and sound levels at various frequencies.

Energy efficiency labels for Systemair K125M Sileo fan, showing F and C ratings

Figure 4.2: Energy Efficiency Labels. Displays the energy class ratings for the basic unit (F) and an optional configuration (C), along with sound power level (29 dB) and airflow (90 m³/h).

5. انسٹالیشن اور سیٹ اپ

The K-series fans are designed for easy duct mounting. Ensure the installation location is suitable and allows for proper airflow and access for maintenance.

Systemair K 125M Sileo duct fan, a cylindrical fan with a control box on top

Figure 5.1: Systemair K 125M Sileo Duct Fan. This image shows the main product view of the cylindrical duct fan with its integrated control box.

5.1 چڑھنا

  • The fan comes with a mounting bracket to facilitate easy installation and removal.
  • All K-fans feature duct connections at least 25 mm long, compliant with EN 1506:1997, for secure attachment to ductwork.
  • For vibration-free connection to the duct system, consider using FK connecting sleeves (available as accessories).
  • The fan can be installed in any mounting position (horizontal, vertical, etc.).
Technical drawing showing dimensions of the Systemair K 125M Sileo fan

Figure 5.2: Dimensions Diagram. This technical drawing illustrates the various dimensions (A, B, C, D, E, F) of the fan, crucial for planning installation space and duct connections.

5.2 الیکٹریکل کنکشن

Connect the fan to a 230V, 50Hz, single-phase power supply. Ensure all wiring is done by a qualified electrician and complies with local regulations. The fan is equipped with an external rotor motor.

6. آپریشن

The Systemair K 125M Sileo fan is designed for continuous operation within its specified parameters.

6.1 سپیڈ کنٹرول

The fan's speed can be controlled to adjust airflow as needed. This can be achieved using:

  • A stepless thyristor controller.
  • A 5-step transformer.

Refer to the performance diagrams to understand the fan's behavior at different operating points.

Performance curves for the Systemair K 125M Sileo fan showing static pressure and power versus volume flow

Figure 6.1: Performance Diagrams. These graphs illustrate the fan's static pressure (P stat.) and power consumption (P) in relation to the volume flow (Q), providing insight into its operational characteristics.

7 دیکھ بھال

The Systemair K 125M Sileo fan is designed to be reliable and largely maintenance-free. However, periodic checks can help ensure optimal performance and longevity.

  • صفائی: Periodically inspect the impeller and housing for dust and debris accumulation. Clean gently with a soft brush or cloth. Ensure power is disconnected before cleaning.
  • معائنہ: تنگی اور پہننے کی علامات کے لیے بجلی کے کنکشن چیک کریں۔
  • بیئرنگ: The fan's motor bearings are typically sealed and do not require lubrication.

8 خرابیوں کا سراغ لگانا

If you encounter issues with your Systemair K 125M Sileo fan, consider the following common troubleshooting steps:

  • Fan not starting: Check the power supply, circuit breaker, and electrical connections. Ensure the thermal contacts have not tripped (they reset automatically).
  • کم ہوا ہوا کا بہاؤ: Inspect ducts for obstructions or leaks. Check if the fan speed controller is set correctly.
  • غیر معمولی شور یا کمپن: Ensure the fan is securely mounted. Check for any foreign objects in the impeller or housing. Verify that the FK connecting sleeves are properly installed if used.
  • زیادہ گرم ہونا: Ensure adequate ventilation around the fan. Check for obstructions that might restrict airflow. The built-in thermal contacts should protect the motor.

If problems persist after performing these checks, contact qualified service personnel or Systemair support.

9. وارنٹی اور سپورٹ

For warranty information, please refer to the terms and conditions provided at the time of purchase or contact your Systemair dealer. Keep your proof of purchase for warranty claims.

For technical support, spare parts, or service inquiries, please contact your local Systemair representative or the seller from whom you purchased the product. Provide the model number (K 125M Sileo) and serial number (if applicable) when seeking support.

متعلقہ دستاویزات - K 125M Sileo

پریview Systemair K 315 L SILEO Centrifugal Duct Fan - Technical Specifications and Dimensions
Detailed technical specifications, dimensions, wiring diagrams, and accessories for the Systemair K 315 L SILEO centrifugal duct fan. Includes performance data, sound levels, and installation information.
پریview Systemair RVK Circular Duct Fan: Installation and Operating Instructions
This guide details the installation, operation, and maintenance of Systemair RVK circular duct fans. It covers safety protocols, electrical connections, commissioning, troubleshooting, and best practices for optimal performance in ventilation systems.
پریview Systemair DXRE/DXRE-D Duct Cooler Installation and Maintenance Manual
This document provides comprehensive installation, mounting, and cleaning instructions for the Systemair DXRE/DXRE-D duct cooler, designed for central cooling of ventilation air and compatible with outdoor units for heating and cooling.
پریview Systemair SAVE VTR 300/B Service & Accessories Installation Manual
Comprehensive guide for installing, configuring, and servicing the Systemair SAVE VTR 300/B heat recovery ventilation unit, covering safety, technical data, operation, and accessories.
پریview Systemair SAVE VTR 150/B Installation Manual
Comprehensive installation manual for the Systemair SAVE VTR 150/B heat recovery ventilation unit. Covers general information, technical specifications, dimensions, mounting procedures for various kitchen hoods, electrical connections, system checks, commissioning, and disposal guidelines.
پریview Systemair SAVE VTR 250/B Installation Manual - Service & Accessories Guide
This manual provides comprehensive installation, service, and accessory information for the Systemair SAVE VTR 250/B heat recovery ventilation unit, detailing technical specifications, configuration, and troubleshooting for optimal performance and air quality.