خریداری کے لیے آپ کا شکریہasing the Coolmay L02S series PLC. This manual mainly explains the product characteristics, general specifications, and wiring methods of this series of PLCs. For detailed programming, please refer to the ‘Coolmay L02S Series PLC Programming Manual”. The L02S series PLC has the following characteristics:

  1. Adopting military-grade 32-bit CPU+ASIC dual processors, supporting online monitoring and downloading, the fastest execution speed of basic instructions reaches 0.24us
  2. Strong scalability, capable of expanding up to 31 1/0 modules, with a maximum 1/0 of 1024 points(modules need to be expanded in the event of a power outagای).
  3. Supports CAN bus and can control servo motion and controller communication that supports CANBIJS (CANOPEN protocol).
  4.  The transistor outputs high-speed pulses with 8-axis YO—Y5 that can reach 100KHz.Supports 8 sets of 100KHz hardware high-speed counters.
  5. Supports special functions such as electronic cam and hand wheel.

برقی پیرامیٹرز

برقی پیرامیٹرز
ان پٹ VOLTAGE DC24V
Digital input indicators
تنہائی کا طریقہ اوپٹوکوپلر
ان پٹ رکاوٹ High speed input terminal 2.4K 0 Normal input terminal 3.3K 0
Input asON The input current at the high-speed input terminal is greater than 5.8mA/24V The input current of the ordinary input terminal isgreater than 9.9mA/24V
Input asOFF The input current at the high-speed input end is less than 4.5mA/19V The input current of the ordinary input terminal is less than 4rnA/17V
فلٹرنگ فنکشن With filtering function, the filtering time canbe set within the range of 0-60ms, with a default of 1Oms
High count function Conventional 8-channel, single-phase 100KHz or 3-channel AB phase 100KHz
ان پٹ کی سطح Passive NPN or PN P, common terminal isolation
Digital relay output indicators Digital transistor output indicators
زیادہ سے زیادہ کرنٹ 2A/point, 4A/4 points COM O.SA/point, 2A/4 points COM
سرکٹ پاور سپلائی والیومtage DC/AC24V~220V DC24V
سرکٹ موصلیت Relay mechanical insulation آپٹوکوپلر موصلیت
جوابی وقت پر about10ms High-speed output: 10µs; others O.Sms
Mechanical lifespan (no load) 10 ملین بار I
 

Electrical lifespan (rated load)

 

300,000 بار

H h-s eedJulse: conventional 8-channel YO-VSis ZOOKHz, Y6-Y7 is lOOKHz. 6, X , an Y1 can’t be used for high-speed and pulse counting simultane- ously, but can be used as regular points.
آؤٹ پٹ لیول Normally open dry contact output, COM can beconnected to positive or negative Low level NPN, COM connected to negative
Analog input indicators Analog output indicators
Analog input/output signals Comes with 2-channel voltage 0- 1 OV and 2-channel current 0-ZOmA Comes with 2-channel voltage 0-lOV and 2-channel current 0-20mA
جوابی وقت 1 اسکین سائیکل I
Number of analog input/ output points 4 چینلز 4 چینلز
درستگی 12 بٹس 12 بٹس
بیرونی انٹرفیس
پروگرام پورٹ Comes with one programming port: Type-C port(faster download speed)
COM پورٹ Comes with 2 RS485,1 RS232,1 CAN, 1 network port
محیط حالت
آپریشن کا درجہ حرارت -20°C~S0°C
رشتہ دار نمی 5%~95%RH (کوئی گاڑھا نہیں)
اسٹوریج کا درجہ حرارت -25°(~ 70°(
کمپن فریکوئنسی 10-57Hz، amplitude 0.035mm; 57Hz-150Hz, acceleration 4.9m/s2 (10 times in X, Y, Z directions, totaling 80 minutes each)

مصنوعات کی ساخت

Coolmay-L02S-Series-Programmable-Controller-fig- (1) Coolmay-L02S-Series-Programmable-Controller-fig- (2) Coolmay-L02S-Series-Programmable-Controller-fig- (3)

ہارڈ ویئر انٹرفیس

Coolmay-L02S-Series-Programmable-Controller-fig- (4)

Attention: S/S is the common terminal for the switch in ut; cx is the common terminal of the switch output; GND is the common terminal for analog input/output
Definition of RS-232 programming port pins

پن سگنل بیان کریں
4 آر ایکس ڈی وصول کریں
5 TXD بھیج رہا ہے
-8 جی این ڈی زمینی تار

Coolmay-L02S-Series-Programmable-Controller-fig- (5)

مواصلاتی بندرگاہ کی تفصیل

  • Serial port 1: RS-232 (PLC programming port): Supports Mitsubishi programming port protocol,Free- port protocol, and MODBUS RTU/ASCII protocol
  • Serial port 2: RS-485 (A1 Bl): Supports Mitsubishi programming port protocol, Freeport protocol, and MODBUS RTU/ASCII protocol.
  • Serial port 3: RS-485 (A B): Supports Mitsubishi programming port protocol, Freeport protocol, and MODBUS RTU/ASCII protocol.
    • When the PLC serves as the host, it supports MODRW instructions, MODRD instructions, and MODWR instructions. CAN (H L) communication port: Supports CANOPEN protocol (communication wiring needs to be connected to the H L above; short circuit the H L below, CAN with terminal resistance of 120 Q; Otherwise, there will be no terminal resistance. Ethernet: Supports programming port protocol, Modbus TCP/UDP protocol, Ethernet/lP protocol.

تنصیب کی ہدایات

بکسوا کی تنصیب
First, open the white buckle, align the expansion interface, and directly push the module in. Press the white buckles on both ends to complete the installationCoolmay-L02S-Series-Programmable-Controller-fig- (7)

Installation method of the guide rail
The CPU module and various expansion modules can be directly installed on the standard rail DIN35mm without the need for a backplane; Press the rail buckle to directly lock the roduct onto the railCoolmay-L02S-Series-Programmable-Controller-fig- (17)

Figure 8: Equivalent Circuit of Card
The L02S series input is a biphasic optocoupler, and users can choose between NPN or PNP connections when using it. However, please n since the common terminals of the input points are all connected, each module or host can only have one wiring method and cannot be mixed.

PLC digital NPN input wiring:
Port short circuit: The S/S of the PLC input terminal is connected to 24V, and the X terminal is connected to the power supply OV, indicating that there is a signal input; Two wire system (magnetic switch): PLC switch input is connected to a two-wire magnetic switch, with the positive pole of the magnetic switch connected to the X terminal and the negative pole connected to OV; Three wire system (photoelectric sensor or encoder): The PLC switch is connected to the photoelectric sensor or encoder of the three wire system. The power supply of the sensor or encoder is connected to the positive pole of the power supply, and the signal line is connected to the X terminal; Encoders and photoelectric sensors require NPN type.Coolmay-L02S-Series-Programmable-Controller-fig- (8)

PLC digital PNP input wiring:
Port short circuit: The S/S of the PLC input terminal is connected to OV, and the X terminal is connected to the 24V power supply, indicating that there is a signal input; Two wire system (magnetic control switch): PLC switch input is connected to a two-wire magnetic control switch, with the negative pole of the magnetic control switch connected to the X terminal and the positive pole connected to 24V; Three wire system (photoelectric sensor or encoder): The PLC switch is connected to the photoelectric sensor or encoder of the three wire system. The power supply of the sensor or encoder is connected to the positive pole of the power supply, and the signal line is connected to the X terminal. The encoder and photoelectric sensor require a PNP type.Coolmay-L02S-Series-Programmable-Controller-fig- (10)

Figure 11 PLC itch PNP wiring

Digital output wiring circuit
شکل 12 ریلے آؤٹ پٹ ماڈیول کے مساوی سرکٹ ڈایاگرام دکھاتا ہے، جس میں آؤٹ پٹ ٹرمینلز کے کئی گروپ ہیں جو ایک دوسرے سے برقی طور پر الگ تھلگ ہیں۔ مختلف گروپوں کے آؤٹ پٹ رابطے مختلف پاور سرکٹس سے جڑے ہوئے ہیں۔Coolmay-L02S-Series-Programmable-Controller-fig- (9)

Figure 12 Equivalent circuit of relay output

The NPN and cx common cathode output type transistors shown in Figure 13 also have several groups of output terminals, which are electrically isolated from each other. The output contacts of different groups can be connected to different power circuits; The transistor output can only be used for DC 24V load circuits.Coolmay-L02S-Series-Programmable-Controller-fig- (11)

Figure 13 Equivalent circuit of transistor output

For inductive loads connected to AC circuits, external circuits should consider RC instantaneous voltage absorption circuits; For the inductive load of the corresponding DC circuit, consideration should be given to adding a freewheeling diode, as shown in Figure 14.Coolmay-L02S-Series-Programmable-Controller-fig- (12)

The wiring of the stepper or servo motor is shown in Figure 15. The L02S series PLC defaults to YO-Y7 as pulse points, and the direction can be customized. (Note: A 2K Q resistor must be connected in series with DC24V for a 5V drive.)Coolmay-L02S-Series-Programmable-Controller-fig- (13)

The L02S-24MT/L02S-24MR host comes with 4 analog inputs and 4 analog outputs; The type of analog input includes 2 sets of 0-1 OV and 2 sets of 0-20mA, The type of analog output includes 2 sets of 0-10V and 2 sets of 0-20mA. As shown in Figure 16.Coolmay-L02S-Series-Programmable-Controller-fig- (14)

PLC ینالاگ وائرنگ
Two-wire system: the positive pole of the power supply is connected to the positive pole of the transmitter, the negative pole of the transmitter is connected to the AD terminal, and the negative pole of the power supply is connected to the GND terminal. Generally, this is the connection method for 0-20mA/4-20mA transmitters; Three-wire system: The positive pole of the power supply is connected to the positive pole of the transmitter, and the negative pole of the power supply and the negative pole of the signal output are the same terminal. The positive and negative poles of the transmitter signal output are respectively connected to the AD terminal and GND terminal Four wire system: Connect the positive and negative poles of the power supply to the positive and negative poles of the transmitter, respectively. Connect the positive and negative poles of the transmitter signal output to the AD and GND terminals, respectively

ٹپس
L02S Series Programmable Controller (PLC) User Manual
Before using this product, please read the relevant manual carefully and use this product within the environmental conditions specified in the instruction manual.

  1. Please power on the product after confirming the power supply voltage range (conventional product power supply DC24V!) and correct wiring to avoid damage.
  2. When installing this product please be sure to tighten the screws or clamp لاتعلقی سے بچنے کے لیے گائیڈ ریل۔
  3. وائرنگ اور کیبل پلگ لگانے سے گریز کریں جب وہ لائیو ہوں، کیونکہ یہ آسانی سے برقی جھٹکا یا سرکٹ کو نقصان پہنچا سکتا ہے۔ جب پروڈکٹ سے بدبو یا غیر معمولی آواز نکلتی ہے، تو براہ کرم فوری طور پر پاور سوئچ کو منقطع کر دیں۔ مشینی سکرو ہولز اور وائرنگ کرتے وقت، دھاتی شیونگ اور تار کے سروں کو کنٹرولر کے وینٹیلیشن ہولز میں نہ آنے دیں، کیونکہ یہ پروڈکٹ کی ناکامی اور غلط کام کا سبب بن سکتا ہے۔
  4. Do not tie the power cord and communication cable together or place them too close. Keep a distance of at least 1 Ocm; Strong and weak electricity need to be separated and properly and effectively grounded; In situations with severe interference, shielded cables should be used for communication and high-frequency signal input and output to improve anti-interference performance. The grounding terminal FG on this machine must be correctly grounded to improve its anti-interference ability.
  5.  The switch input is powered by external DC24V, and the input signal is isolated from the power supply. It supports PNP or NPN connection and can choose one wiring method during use. It does not support mixed connection, otherwise it may cause damage to the machine.
  6. The cx of the output common terminal of the switching transistor is a common cathode, and the common terminal of the relay is not limited.
  7.  براہ کرم پروڈکٹ کو جدا نہ کریں یا اپنی مرضی سے وائرنگ میں ترمیم نہ کریں۔ بصورت دیگر، یہ خرابیوں، غلط کاموں، نقصانات اور آگ کا سبب بن سکتا ہے۔
  8.  When installing and disassembling the product, please be sure to cut off all power sources, otherwise it will cause equipment malfunction and failure.

پیارے کسٹمر:
مصنوعات کی وارنٹی ہدایات
Sincerely thank you for choosing this product. As our user, you will receive our company’s high-quality service of “free repair service and lifelong technical support for product quality problems caused by non-human damage or disassembly within two years from the date of purchase (LCD screen and touchpad for one and a half years).” During the warranty period, if there is a hardware malfunction caused by the product itself, our company will provide customers with free replacement or repair services. Do not disassemble or repair the product on your own. Our company’s products are labeled with anti-disassembly labels, and only our company and authorized professionals can repair our products. Any unauthorized disassembly or repair by other personnel is equivalent to automatically waiving the warranty service provided by our company.

The following situations do not fall within the scope of free warranty services:

  • Damage caused by human factors (external impact or collision, improper use, etc.)
  • Unauthorized disassembly, modification, or repair of the product
  • Damage caused by external factors (such as lightning strikes,
  • water ingress into the power supply, falling, etc.)
  • Damage caused by incorrect installation or use by the user
  • The equipment has expired its warranty service period

Shenzhen Coolmay Technology Co., Ltd
ٹیلی فون: +86 19925291353
ای میل:cm2@coolmay.net
Web:en.coolmay.com
v 2025/ 09
The model specifications and information related to the product in this manual are subject to change without prior notice

Coolmay-L02S-Series-Programmable-Controller-fig- (15)

علی بابا

Coolmay-L02S-Series-Programmable-Controller-fig- (16)

علی ایکسپریس

دستاویزات / وسائل

Coolmay L02S سیریز قابل پروگرام کنٹرولر [پی ڈی ایف] یوزر مینوئل
LO2S، L02S سیریز قابل پروگرام کنٹرولر، L02S سیریز، قابل پروگرام کنٹرولر، کنٹرولر

حوالہ جات

ایک تبصرہ چھوڑیں۔

آپ کا ای میل پتہ شائع نہیں کیا جائے گا۔ مطلوبہ فیلڈز نشان زد ہیں۔ *